TC-100 Turbine controller MODBUS registers
Loading...
Searching...
No Matches
Rotary atomizer controller TC-100. MODBUS Registers

Controller support RS-485 Modbus RTU:
Data – 8bit; Stop bit – 1; None parity;
Baud rate: 9600, 19200(Default), 38400, 115200; Device: 1-127 (Default 100)
Supported functions: 03 Read Holding Registers, 06 Preset Single Register, 16 (10 Hex) Preset Multiple Registers

Registers

Address Register Data Type Range Default Value Data Description
0x01 Device ID RO 0-65535 0xc100
0x02 Software version RO 0-65535
0x03 Control RW Bits 1:0 MODE[1:0]: Turbine mode
- 00: stop
- 01: speed 1
- 10: speed 2
- 11: (speed 1 + speed 2)/2
0x04 Status RO Bit 0 RUN: Turbine running
Bit 1 RDY: Actual speed > Ready speed
Bit 2 TSR: Target speed reached
Bit 7 AERR: Any error
Bit 8 CERR: Communication error
Bit 9 TOUT: Timeout error
0x05 Actual speed RO 0-65535 RPM Bits [15:0] ASPD: Actual speed
0x06 Actual pressure RO 0-10000 Bar*1000 Bits [15:0] APR: Actual pressure
0x07 Pressure set point RO 0-10000 Bar*1000 Bits [15:0] PSP: Pressure set point
0x08 Speed 1 RW Backup 0-60000 RPM 30000 RPM Bits [15:0] SPD1: Speed 1
0x09 Speed 2 RW Backup 0-60000 RPM 40000 RPM Bits [15:0] SPD2: Speed 2
0x0a Speed tolerance RW Backup 1-30% 10% Bits [15:0] SPDT: Ready speed = ASPD*(100-SPDT)/100
0x0b PID Kp RW Backup 0-65535 2500 Bits [15:0] PIDKP: PID Kp
0x0c PID Ki RW Backup 0-65535 400 Bits [15:0] PIDKP: PID Ki
0x0d PID Kd RW Backup 0-65535 3500 Bits [15:0] PIDKP: PID Kd
0xf0 Baud rate RW 0-65535 0 Bits [15:0] BAUD: Baud rate
- 0: 9600
- 1: 19200
- 2: 38400
- 3: 115200
0xf1 Device Address RW Backup 0-247 115 Bits [16:0] DEVADDR: Device Address
Device Address - 0-247

RO - read only memory, RW - read-write memory, Backup - battery powered memory